Programma EGIL Circuit Breaker Analyser

The Programma EGIL is an automatic timer and motion analyzer for medium- and high-voltage substation circuit breakers. It is intended for use on circuit breakers with one contact per phase. EGIL incorporates features commonly found on more complex test systems, but is designed to be smaller, simpler to use and less expensive than other similar test sets. It’s price makes it attractive to smaller utilities and it is an ideal supplementary product for maintenance departments at larger power companies and for testing contractors.

General Specifications

  • Mains voltage 115/230 V AC (switchable), 50/60 Hz.
  • Display LED.
  • Mains voltage 115/230 V AC (switchable), 50/60 Hz.
  • Power consumption 100 VA (max).
  • Time measurement Measurement time: 1 to 100 s
  • Resolution: 0.1 to 10 ms.
  • Number of channels 3 with common ground.
  • Time base inaccuracy 0.05% of the reading ± resolution.
  • Status thresholds Closed: < 10 Ω ± 20%
  • Resistor: 10 Ω ± 20% to 3 kΩ ±20%
  • Open: > 3 kΩ ± 20%.
  • Open circuit voltage 24 V ± 20%.
  • Short circuit current 100 mA ± 20%.
  • AUX 1 & 2 Number of channels: 2, galvanically isolated.
  • Contact-sensing (Dry) Status thresholds
  • Closed < 600 Ω ± 30%.
  • Open > 600 Ω ± 30%.
  • Open circuit voltage 20 V ± 20% DC.
  • Short circuit current 25 mA ± 20%.
  • Voltage sensing (Wet) Status thresholds
  • Open indication < 8 V (polarity insensitive).
  • Close indication > 13 V (polarity insensitive).
  • Working voltage 250 V AC/DC.
  • Current measurement Range: ± 25 A per channel.
  • Resolution: 25 mA.
  • Inaccuracy: 1% of the reading ±100 mA.
  • Working voltage: 250 V AC / DC.
  • Breaker operation Sequences: C, O, C-O, O-C, O-C-O.
  • Continuous current 5 A.
  • Max current 25 A during 300 ms, rest time 1 min.
  • Contact function Two independent control functions.
  • Contact characteristics Non bouncing, closing time max. 0.1 ms.
  • Make/Break capacity 25 A, 250 V (AC or DC) per contact function.
  • Start breaker operation By rotary switch.
  • Pulse length Adjustable in steps of 10 ms.
  • Pulse delay Adjustable in steps of 10 ms.
  • Working voltage 250 V AC / DC.
  • Printout Type of printout: Graphic and numeric.
  • Printer Thermal printer with fixed print head.
  • Graphic resolution 8 dots/mm – 203 dpi.

Payment must be completed with a confirmed bank method.

The system was removed from an operational facility, it powers and did respond from pressing buttons, we weren't able to test it beyond that as the system functionality is too much to use on our buildings circuitry as a result we are offering this unit as we received known to power on, but with no warranty beyond that.